Model |
INEHA-200-6-C |
INEHA-1725-6-C |
IPEHA-1575-6-C |
IPEHA-1375-6-C |
AC side parameters |
||||
Rated output power (kW) |
200 |
1725 |
1575 |
1375 |
Wiring mode |
Three-phase three-wire, IT system |
|||
Output overload capacity (times) |
1.1 @ long term; 1.2 @ 1min |
|||
AC rated current (A) |
168A @ 45 ℃ |
1443A @ 45 ℃ |
||
Allowable grid voltage (Vac) |
690(-15% ~ 15%) |
690(-15% ~ 15%) |
630(-15% ~ 15%) |
550(-15% ~ 15%) |
Allowable grid frequency (Hz) |
50/60(-2.5~1.5) |
|||
Total current harmonic distortion rate |
≤ 3% (rated power) |
|||
Rated power factor |
> 0.99 |
|||
Output voltage distortion |
≤ 3% (linear rated power load) |
|||
DC side parameters |
||||
Maximum DC power (kW) |
224 |
1935 |
1770 |
1548 |
DC voltage range (Vdc) |
1000~1500 |
1000~1500 |
915~1500 |
800~1500 |
Maximum current (A) |
224 |
1935 |
||
DC side withstand short-circuit surge current |
50kA @ 2ms |
|||
Communication Interface |
||||
Communication Interface |
CAN2.0, RS485, and EtherCAT |
|||
Communication Protocol |
Ethercat, ModbusRTU, Modbus-TCP, CAN2.0B, IEC104, IEC61850 |
|||
BMS Access |
Have (passive dry contact) |
|||
Protection |
||||
AC and DC side lightning protection |
Have |
|||
DC side insulation protection |
Have |
|||
AC leakage current protection |
Have |
|||
AC side protection |
Over-current, over-voltage, frequency |
|||
DC side protection |
Over-current, over-voltage, short circuit, reverse polarity protection |
|||
Over-temperature protection |
Have |
|||
AC phase sequence adaptive |
Have |
|||
Power module (IGBT) protection |
Have |
|||
Communication fault protection |
Have |
|||
Cooling system fault protection |
Have |
|||
Fault recording |
Not less than 4 cycles, 256 points per week |
|||
Active Islanding Detection |
Have |
|||
System parameters |
||||
Main circuit topology |
Three-level interleaved parallel |
|||
Operation mode |
Support constant power, constant voltage, constant current control |
|||
Number of parallel machines |
16 |
2 |
||
Other functions |
PQ, VF, SVG, VSG, Black Start |
|||
Grid-connected and off-grid switching |
Optional |
|||
EMI filtering on AC/DC side |
Have |
|||
Maximum system efficiency |
≥ 99% |
|||
Charge-discharge conversion time (ms) |
≤ 50ms |
|||
Weight (Kg) |
≤ 100 |
≤ 3000 |
||
Dimensions (W × D × H) |
680 × 850 × 275 |
|||
Noise (dB) |
<80 |
|||
Protection level |
IP65 |
|||
Anti-corrosion grade |
Meet C4 or C5M requirements of neutral salt spray test by option |
|||
Allowable ambient temperature (℃) |
-30 to 60 |
|||
Cooling mode |
forced air cooling |
|||
Permissible relative humidity |
0 ~ 95% (no condensation) |
|||
Allowable Altitude |
No derating below 2000m; derating operation from 2000m to 4000m |