Model |
NEPC-25kW/52kWh |
INEPC-55kW/108kWh |
INEPC-100kW/215kWh |
AC output |
|||
Rated power |
25kW |
50kW |
100kW |
Maximum output power |
50kW |
60kW |
110kW |
PCS Output Voltage |
400VAC |
400VAC |
400VAC |
Frequency range |
50 to 60Hz |
50 to 60Hz |
50 to 60Hz |
Rated AC current |
36A @ 45 ℃ |
72A @ 45 ℃ |
144A @ 45 ℃ |
Charge-discharge conversion time |
50ms |
50ms |
50ms |
PCS Peak Efficiency |
≥ 97.3% |
≥ 97.3% |
≥ 97.3% |
Type of grid connection |
3W + PE or 3W + N + PE |
3W + PE or 3W + N + PE |
3W + PE or 3W + N + PE |
Overload capacity |
120%, 1min; 150%, 10s |
120%, 1min; 150%, 10s |
120%, 1min; 150%, 10s |
Fire protection system |
|||
Salt spray alarm |
Salt spray sensor |
Salt spray sensor |
Salt spray sensor |
Aerosol fire extinguisher |
Capacity: 3kg |
Capacity: 3kg |
Capacity: 3kg |
Oxidant |
FM200 or NC1230 |
FM200 or NC1230 |
FM200 or NC1230 |
Battery System |
|||
System energy |
52.096kWh |
108.928kWh |
215.04kWh |
Nominal capacity |
148Ah |
148Ah |
280Ah |
Nominal voltage |
352V |
736V |
768V |
Battery working voltage range maximum charge and discharge current |
330V ~ 396V |
690V ~ 828V |
672V ~ 852V |
System energy |
82ADC |
82ADC |
150ADC |
System parameters |
|||
Cooling mode |
By air cooling, air conditioning or heat exchanger |
By air cooling, air conditioning or heat exchanger |
By air cooling, air conditioning or heat exchanger |
Noise |
<70dB |
<70dB |
<70dB |
Operating humidity |
0 ~ 95% (non-condensing) |
0 ~ 95% (non-condensing) |
0 ~ 95% (non-condensing) |
Protection level |
IP54 |
IP54 |
IP54 |
Operating temperature |
20 ℃ ~ +60 ℃ |
-20 ℃ ~ +60 ℃ |
-20 ℃ ~ +60 ℃ |
Man-machine interface |
LCD |
LCD |
LCD |
Altitude |
Maximum 4000m (derating operation above 2000m) |
Maximum 4000m (derating operation above 2000m) |
Maximum 4000m (derating operation above 2000m) |
Weight of whole machine |
About 2800kg |
About 2800kg |
About 2800kg |
Dimensions (W * D * H) |
1500*1000*2300mm |
1500*1000*2300mm |
1500*1000*2300mm |
Communication mode |
RS485,CAN, Ethernet, dry contact |
RS485,CAN, Ethernet, dry contact |
RS485,CAN, Ethernet, dry contact |
Isolation mode |
Non-isolated (optional transformer) |
Non-isolated (optional transformer) |
Non-isolated (optional transformer) |