Rated Voltage |
kV |
40.5 |
Rated Insulation Level |
|
|
Power Frequency Withstand Voltage |
|
|
Dry |
kV |
95 |
Wet |
kV |
80 |
Lightning Impulse Withstand Voltage (Peak) |
kV |
185 |
Rated Current |
A |
1250, 1600, 2000 |
Rated Short-Circuit Breaking Current |
kA |
20, 25, 31.5 |
Rated Operating Sequence |
|
Open-0.3s-Close Open-180s-Close Open |
Rated Short-Circuit Current Breaking Times |
Times |
12 |
Rated Short-Circuit Closing Current (Peak) |
kA |
50, 63, 80 |
Rated Peak Withstand Current |
kA |
50, 63, 80 |
Rated Short-Time Withstand Current |
kA |
20, 25, 31.5 |
Rated Duration of Short-Circuit Current |
s |
4 |
Average Opening Speed |
m/s |
1.5 ± 0.2 |
Average Closing Speed |
m/s |
0.7 ± 0.2 |
Contact Closing Bounce Time |
s |
≤2 |
Three-Phase Synchronization Time Difference |
s |
≤2 |
Closing Time |
s |
≤150 |
Opening Time |
s |
≤60 |
Mechanical Lifespan |
Times |
10,000 |
Rated Operating Voltage and Auxiliary Circuit Voltage |
V |
DC 220, 110, 24 |
Rated Operating Voltage and Auxiliary Circuit Voltage |
V |
AC 220, 110, 24 |
DC Resistance of Each Phase Circuit (excluding transformers) |
μΩ |
≤100 |
Allowable Wear Thickness of Moving and Static Contacts |
mm |
3 |
Weight |
kg |
800 |