GSR6-27.5 series environmentally friendly gas-insulated metal-enclosed switchgear (C-GIS) uses dry air (D-air) as the insulating medium. It is a new generation of MV equipment assemblies integrating vacuum arc extinguishing technology, APG solid insulation technology, gas insulation technology and interface insulation technology. The product solution is mainly suitable for electrified railway systems with single-phase or two-phase, rated voltage 27.5kV and a maximum voltage of 31.5kV, such as high-speed railways, passenger dedicated lines and other high-level railway fields.
The product has a modular design, and the solution can be flexibly combined according to the needs of railway users. The products are provided with a sealed pressure system. All the HV live parts of the main circuit are sealed in the stainless-steel gas tank, which is not affected by the environment. The products have the characteristics of intelligence, reliable operation, small size and maintenance-free.
No. |
Name |
Unit |
Parameter |
||
1 |
Rated voltage |
kV |
1×31.5 |
2×31.5 |
|
2 |
Rated frequency |
Hz |
50 |
||
3 |
Lightning impulse withstand voltage |
Pole to ground, circuit breaker break |
kV |
200 |
200 |
Between poles |
/ |
325 |
|||
Isolating fracture |
220 |
220 |
|||
4 |
Main circuit power frequency withstand voltage (1min) |
Pole to ground, circuit breaker break |
kV |
95 |
95 |
Between poles |
/ |
140 |
|||
Isolating fracture |
118 |
118 |
|||
5 |
Insulating medium |
|
Dry air |
||
6 |
Gas filled compartment zero gauge pressure 5min power frequency withstand pressure |
|
1.3Ur |
||
7 |
Rated current of the main busbar/feeder line |
A |
1250, 1600, 2000, 2500 |
||
8 |
Rated short-time withstand current/duration |
kA/s |
31.5/4 |
||
9 |
Rated peak withstand current/grounding switch closing current |
kA |
80 |
||
10 |
Internal arc withstand capability AFL |
kA/s |
31.5/1 |
||
11 |
Level of protection |
Inflatable box |
|
IP65 |
|
Switchgear |
IP54 |
||||
12 |
Rated inflation pressure (20°C gauge pressure) |
MPa |
|
||
13 |
Annual air leakage rate |
% |
≤0.1 |
||
14 |
Overall dimensions |
Width |
mm |
600/900 |
|
Height |
mm |
2600 |
|||
Depth |
mm |
1900 |
Table 2 Technical parameters of operation mechanism
Name |
Unit |
Parameter |
Rated operation sequence |
/ |
O-0.3s-CO-180s-CO |
Mechanical life |
Time (s) |
10000 |
Energy storage motor rated voltage |
V |
DC110, DC220 |