This product is suitable for wiring in control, signal, protection, and measurement systems with a rated voltage of 450/750V and below.
1. Standards:
- This product is manufactured according to GB/T 9330-2020 "Plastic Insulated Control Cable" and enterprise standards.
2. Application:
- It is suitable for wiring in control, signal, protection, and measurement systems with a rated voltage of 450/750V and below.
3. Features:
-
Rated Voltage (U0/U): 450/750V.
-
Maximum Operating Temperature of Cable Conductor:
- PVC Insulation: 70°C.
- XLPE Insulation: 90°C.
-
Maximum Conductor Temperature During Short Circuit:
- XLPE Insulation: 250°C (maximum duration not exceeding 5 seconds).
- PVC Insulation: 160°C (maximum duration not exceeding 5 seconds).
-
Installation Temperature: The ambient temperature during cable installation should not be lower than 0°C.
-
Recommended Minimum Bending Radius:
- Cables without armor should have a bending radius of not less than 6 times the cable's outer diameter.
- Cables with armor or copper tape shielding should have a bending radius of not less than 12 times the cable's outer diameter.
- Flexible cables with a shielding layer should have a bending radius of not less than 6 times the cable's outer diameter.
4. Product Models: KVV, KVVP, KVV22, and various other models.